3. Temperature measurements Infrared thermo-vision inspection of arresters is a frequently used multipurpose substation maintenance technique, including for arresters. Indeed,experience shows that thermal imaging can be effectively used to track surge arrester degradation. However, such measurements are indicative only to the extent that they are sensitive enough to identify increased block temperature by detecting its impact on the surface of the arrester housing