Shutdown Generator
1. Before shutting down generator, it must first be unloaded by decreasing the speed in increment while at the same time, the oncoming generator is being loaded up. When the load on the generator to be shutdown approaches 100-150 Kw. The generator breaker should be manually tripped out.
2. Take few minute times to ensure power system is stabilized, put generator on idle speed for cool down for a while then stop the engine.
Allow the engine to run idle by switch to idle 900 rpm for 5 minutes.
Press the “STOP” pushbutton at the local control panel
The enclosure vent fan and the radiator fan will continue to run for a predetermined period after the engine is stopped
Close fuel gas supply valve
1. Close lube oil ball valve to feeding valve.