CHAPTER 4
INDIVIDUAL BUILDING MNS FOR NEW CONSTRUCTION PROJECTS
4-1 SCOPE. Individual building MNS are intended to provide real-time information
to personnel within and in the immediate vicinity of buildings on a DOD installation.
These systems are required by UFC 4-010-01 for new construction and renovation of
existing buildings. This chapter provides the design criteria for new construction
projects. It discusses the requirements of the individual building MNS that is installed in
new construction as part of a combined MNS/fire alarm system.
Note: In most cases, the simplest and most economical approach for new construction
will be to install a combined system that performs both as an individual building MNS
and as the building fire alarm/voice evacuation system.
4-2 REQUIREMENTS FOR SYSTEM DESIGNERS. The individual building MNS
shall be designed under the supervision of a registered fire protection engineer, by a
registered professional engineer having at least four years of current experience in the
design of fire protection and detection systems, or by an engineering technologist
qualified at NICET Level IV in fire alarm systems. The individual’s name, signature, and
professional engineer number or NICET certification number shall be included on all
final design documents.
Navy systems shall be designed only by a registered fire protection engineer who
has passed the fire protection engineering written examination administered by the
National Council of Examiners for Engineering and Surveys (NCEES).
4-3 SYSTEM OVERVIEW. A combined system is required by the Navy and is
highly recommended by the Army and Air Force. The combined system design may be
used by the Marine Corps when specifically approved by the AHJ based on the class
and size of the building requiring the MNS. Otherwise, Marine Corps projects will use
the technical criteria of Chapter 5. If an Army or Air Force installation approves use of a
separate MNS and separate building fire alarm system in a new construction project,
use the technical criteria of Chapter 5.
A separate MNS may be installed in Navy projects for a building not provided with a
fire alarm system. See Chapter 5.
Note: See paragraph 6-5 for MNS requirements for special occupancies such as
medical facilities and facilities intended for occupancy by persons not capable of
self-preservation.
4-3.1 Subsystems. An individual building MNS for new construction projects
includes several subsystems: autonomous control unit (ACU); local operating consoles
(LOC); notification appliance network; and interface with the wide area MNS on the
DOD installation. System design and wiring is designed to meet NFPA 72 requirements
for MNS and fire alarm systems.
UFC 4-021-01
9 April 2008
Change 1, January 2010
22
4-3.2 ACU
4-3.2.1 Functions. The ACU is used to monitor and control the notification appliance
network. At the ACU, personnel in the building can initiate delivery of pre-recorded voice
messages, provide live voice messages and instructions, and initiate visual strobe and
alphanumeric message notification appliances. Actions taken at the ACU take
precedence over actions taken at any other location, including the LOC, or inputs from
the wide area MNS on the DOD installation.
4-3.2.2 Combined System. For new construction, the ACU shall be integrated with
the building fire alarm control panel (FACP) to form one combined system that performs
both functions. The building PA system for smaller buildings may be integrated with the
combined system so that all three functions—mass notification, fire alarm, and PA—are
provided by one building system. In large buildings, however, combining the PA system
will typically require the design of very complex speaker switching matrices and is not
recommended. Combined systems shall meet the requirements of NFPA 72.
Note: A combined system may include an ACU and FACP supplied from different
manufacturers or placed in separate equipment enclosures; however, the ACU and
FACP must be integrated in their controls and performance to meet the requirements of
NFPA 72 and this UFC.
Note: The Army and Air Force permit the MNS and fire alarm system to be installed as
separate systems if mandated by the DOD installation. The Marine Corps normally
requires the MNS and fire alarm system to be installed as separate systems unless
specifically permitted by the AHJ. See Chapter 5 for technical criteria for this design
approach.
4-3.3 LOC. A LOC is a unit designed to allow emergency response forces and
building occupants to operate the individual building MNS, including initiating delivery of
pre-recorded voice messages, providing live voice messages and instructions, initiating
visual strobe and alphanumeric message notification appliances, overriding external
voice announcements, and terminating mass notification functions. A LOC is usually
contained in a small, wall-mounted enclosure. Not all functions that could be performed
at the ACU are necessarily available at a LOC.
4-3.4 Notification Appliance Network. A notification appliance network consists of
a set of audio speakers, strobes, and text signs (when required) that are located to alert
occupants and provide intelligible voice and visual instructions.
4-3.4.1 Audio Appliance Network. Speakers are provided at all locations in the
building and also around the building at entrances/exits and other outdoor areas (such
as courtyards) commonly used by the building occupants. Important design
considerations for the audio speakers include intelligibility and audio intensity.
Note: Outside notification more than 5 m (16 ft) from the building should be provided by
the wide area MNS.
UFC 4-021-01
9 April 2008
Change 1, January 2010
23
4-3.4.1.1 Intelligibility is defined in NFPA 72. Commercially available test
instrumentation shall be used to verify intelligibility.
4-3.4.1.2 Effective voice communication within buildings occurs by using a system
design of many speakers, each with low audio intensity.
4-3.4.2 Visual Appliance Network. Strobes are provided at all locations inside the
building to meet the accessibility requirements of 1 ABAAG /1/ for persons with
hearing disabilities. Strobes are provided at the same locations in a building that would
be required for a fire alarm system notification appliance. Combined MNS/FACP
systems may use either one strobe (clear) or two strobes (clear for fire and amber for
MNS) as specified by the AHJ.
4-3.4.2.1 Navy installations shall use one clear strobe and also shall provide text signs.
Text signs are required over the door to each egress stairwell and over (or adjacent to)
the substantial means of egress from the level of discharge. Exterior exit doors from a
single room (e.g., mechanical or electrical rooms) do not require a text sign.
4-3.4.2.2 Army and Air Force installations shall use a clear strobe for fire and an amber
strobe for MNS. Use of text signs is optional and at the discretion of the DOD
installation. If provided, text signs shall be located over the door to each egress stairwell
and over (or adjacent to) the substantial means of egress from the level of discharge.
Exterior exit doors from a single room (e.g., mechanical or electrical rooms) do not
require a text sign.
4-3.4.2.3 Marine Corps installations shall contact the AHJ for guidance on visual
notification appliances.
4-3.5 Interfaces with the Wide Area MNS. If a wide area MNS is provided on the
DOD installation, the individual building MNS communicates with the central control
units of the wide area MNS to provide status information, receive commands, activate
pre-recorded messages, and originate live voice messages. If no wide area MNS is
provided on the DOD installation, at a minimum, the individual building MNS shall be
able to receive an audio line-level input.
4-3.6 Logical Block Diagrams. Figures 4-1 and 4-2 show the logical block
diagrams for acceptable configurations of the individual building MNS for new
construction.
Note: These diagrams are intended to show only the functional relationships of the
major components. They are not intended to serve as wiring diagrams. Many essential
design features for an operational system, such as end-of-line resistors, are not shown.
UFC 4-021-01
9 April 2008
Change 1, January 2010
24
Figure 4-1. Individual Building Mass Notification System:
Combination Fire Alarm System and MNS (Navy)
BATTERY
BACKUP
COMBINED
FIRE
ALARM
CONTROL
PANEL
&
AUTONOMOUS
CONTROL
UNIT
SPEAKERS
STROBES (WHITE/CLEAR)
DISPLAYS (REQUIRED – NAVY)
LOCAL OPERATING CONSOLE(S) (IF USED)
Conductor Integrity
Monitoring Required
Wide Area MNS
(if existing)
Note
Combined
System –
could use
one or more
enclosures
as listed
UFC 4-021-01
9 April 2008
Change 1, January 2010
25
Figure 4-2. Individual Building Mass Notification System:
Combination Fire Alarm System and MNS (Army and Air Force)
BATTERY
BACKUP
COMBINED
FIRE
ALARM
CONTROL
PANEL
&
AUTONOMOUS
CONTROL
UNIT
Conductor Integrity
Monitoring Required
LOCAL OPERATING CONSOLES
SPEAKERS
STROBES (AMBER)
STROBES (WHITE/CLEAR)
DISPLAYS (OPTIONAL)
Note
Combined
System –
could use
one or more
enclosures
Wide Area MNS as listed
(if existing)
UFC 4-021-01
9 April 2008
Change 1, January 2010
26
4-4 ACU
4-4.1 Locations. The ACU shall form a combined system with the FACP. These
control panels may be co-located in the same enclosure or may be physically
separated. If they are located in the same enclosure, install the enclosure at the location
normally specified by the DOD component AHJ for a stand-alone FACP.
4-4.2 Design Features. The ACU shall:
• Be able to function independently upon failure of the wide area MNS (if
provided on the DOD installation).
• Be a listed combination system with the fire alarm system as described in
NFPA 72 and meeting UL Standard 864 and the specific requirements of this
UFC. The listing evaluation shall be accomplished by UL, Factory Mutual
Research Corporation (FM), or another nationally recognized testing
laboratory (NRTL).
N
Results (
Thai) 1:
[Copy]Copied!
บทที่ 4แต่ละอาคาร MNS สำหรับโครงการก่อสร้างใหม่ขอบเขต 4 1 แต่ละอาคาร MNS มีวัตถุประสงค์เพื่อให้ข้อมูลในเวลาจริงให้บุคลากรภายใน และ ในบริเวณใกล้เคียงอาคารที่ติดตั้งแบบ DODระบบเหล่านี้จำเป็น โดย UFC 4-010-01 สำหรับการก่อสร้างใหม่และปรับปรุงอาคารที่มีอยู่ บทนี้แสดงเกณฑ์การออกแบบก่อสร้างใหม่โครงการ ได้กล่าวถึงความต้องการของแต่ละอาคาร MNS ที่ติดตั้งในก่อสร้างใหม่เป็นส่วนหนึ่งของระบบเตือนภัยของ MNS/ไฟ รวมหมายเหตุ: ในกรณีส่วนใหญ่ วิธีที่ง่ายที่สุด และประหยัดที่สุดสำหรับการก่อสร้างใหม่จะติดตั้งระบบรวมที่ทำงานทั้งเป็นที่แต่ละอาคาร MNSและ เป็นการสร้างระบบเตือนไฟไหม้/เสียงอพยพความต้องการ 4-2 การออกแบบระบบ อาคารละ MNSจะถูกออกแบบมาภายใต้การดูแลของวิศวกรป้องกันไฟทะเบียน โดยวิศวกรมืออาชีพลงทะเบียนไม่น้อยกว่า 4 ปีประสบการณ์ปัจจุบันในการออกแบบระบบป้องกันและตรวจจับไฟ หรือเทคโนโลยีการการวิศวกรรมคุณสมบัติที่ IV ระดับ NICET ในระบบเตือนอัคคีภัย ชื่อของแต่ละบุคคล ลายเซ็น และวิศวกรมืออาชีพหมายเลขหรือหมายเลขใบรับรอง NICET จะรวมอยู่ในทั้งหมดออกแบบขั้นสุดท้ายเอกสารนี้ระบบกองทัพเรือจะถูกออกแบบมาเฉพาะ โดยเพลิงทะเบียนวิศวกรที่แล้ววิศวกรรมป้องกันอัคคีภัยที่เขียนตรวจสอบดูแลโดยสภาแห่งชาติของนายวิศวกรรมและแบบสำรวจ (NCEES)ภาพรวมระบบ 4-3 ระบบรวมจำเป็นต้องใช้กองทัพเรือ และเป็นขอแนะนำ โดยกองทัพบกและกองทัพอากาศ การออกแบบระบบรวมอาจใช้ โดยนาวิกโยธินเมื่อคณะ AHJ ตามชั้นเรียนโดยเฉพาะและขนาดของอาคารที่ต้องการ MNS มิฉะนั้น โครงการนาวิกโยธินจะใช้เงื่อนไขทางเทคนิคของบทที่ 5 ถ้าการติดตั้งที่กองทัพบกหรือกองทัพอากาศอนุมัติใช้เป็นMNS แยกและแยกอาคารในโครงการก่อสร้างใหม่ ระบบป้องกันอัคคีภัยใช้เงื่อนไขทางเทคนิคของบทที่ 5MNS แยกอาจถูกติดตั้งในโครงการกองทัพเรือสำหรับอาคารที่ไม่มีการระบบเตือนไฟไหม้ ดูบทที่ 5หมายเหตุ: ดูความ MNS 6 ย่อหน้า-5 occupancies พิเศษเช่นสิ่งอำนวยความสะดวกทางการแพทย์และสิ่งอำนวยความสะดวกไว้สำหรับการเข้าพัก โดยบุคคลที่ไม่สามารถself-preservationที่ย่อย 4 3.1 อาคารการละ MNS สำหรับโครงการก่อสร้างใหม่มีหลายย่อย: หน่วยควบคุมอิสระ (ACU); ภายในคอนโซลการดำเนินงาน(ล็อค); เครือข่ายอุปกรณ์แจ้งเตือน และอินเทอร์เฟซ MNS พื้นที่กว้างในการติดตั้ง DOD ออกแบบระบบและสายถูกออกแบบมาเพื่อตอบสนองข้อกำหนดของ NFPA 72MNS และระบบเตือนอัคคีภัยUFC 4-021-019 2551 เมษายนเปลี่ยนแปลง 1, 2553 มกราคม224 3.2 ACUหน้าที่ 4-3.2.1 ACU ที่ใช้ในการตรวจสอบ และควบคุมอุปกรณ์แจ้งเตือนเครือข่าย ที่ ACU บุคลากรในอาคารสามารถเริ่มส่งเสียงที่บันทึกไว้ล่วงหน้าmessages, provide live voice messages and instructions, and initiate visual strobe andalphanumeric message notification appliances. Actions taken at the ACU takeprecedence over actions taken at any other location, including the LOC, or inputs fromthe wide area MNS on the DOD installation.4-3.2.2 Combined System. For new construction, the ACU shall be integrated withthe building fire alarm control panel (FACP) to form one combined system that performsboth functions. The building PA system for smaller buildings may be integrated with thecombined system so that all three functions—mass notification, fire alarm, and PA—areprovided by one building system. In large buildings, however, combining the PA systemwill typically require the design of very complex speaker switching matrices and is notrecommended. Combined systems shall meet the requirements of NFPA 72.Note: A combined system may include an ACU and FACP supplied from differentmanufacturers or placed in separate equipment enclosures; however, the ACU andFACP must be integrated in their controls and performance to meet the requirements ofNFPA 72 and this UFC.Note: The Army and Air Force permit the MNS and fire alarm system to be installed asseparate systems if mandated by the DOD installation. The Marine Corps normallyrequires the MNS and fire alarm system to be installed as separate systems unlessspecifically permitted by the AHJ. See Chapter 5 for technical criteria for this designแนวทางการLOC. 4-3.3 ล็อคเป็นหน่วยออกมาตอบโต้กองกำลัง และสร้างครอบครัวมี MNS รวมถึงการเริ่มจัดส่งของแต่ละอาคารข้อความเสียงที่บันทึกไว้ล่วงหน้า การให้คำแนะนำ เริ่มต้นและข้อความเสียงสดภาพแฟลชและอุปกรณ์แจ้งเตือนข้อความอักษร แทนภายนอกเสียงประกาศ และสิ้นสุดฟังก์ชันการแจ้งเตือนโดยรวม ล็อคเป็นปกติอยู่ในตู้ขนาดเล็ก ติดผนัง ฟังก์ชันทั้งหมดที่สามารถทำได้ที่ ACU มีจำเป็นต้องมีการ LOC.เครือข่ายอุปกรณ์แจ้งเตือน 4-3.4 อุปกรณ์แจ้งเตือนเครือข่ายประกอบด้วยชุดลำโพง strobes และป้ายข้อความ (เมื่อจำเป็น) ที่ได้รับการแจ้งเตือนครอบครัว และให้คำแนะนำภาพและเสียง intelligible4 3.4.1 เครือข่ายอุปกรณ์เสียง ลำโพงมีพื้นที่ทั้งหมดในการอาคาร และ รอบอาคารภายนอกพื้นที่อื่น ๆ (เช่นการที่ทางเข้า/ออกจากเป็นสนามหญ้า) ใช้งาน โดยการจัดสร้าง ออกแบบที่สำคัญข้อควรพิจารณาสำหรับลำโพงที่มีความเข้มเสียง intelligibilityหมายเหตุ: นอกแจ้ง มากกว่า 5 เมตร (16 ฟุตจากอาคาร)ควรให้บริเวณกว้าง MNSUFC 4-021-019 2551 เมษายนเปลี่ยนแปลง 1, 2553 มกราคม234 3.4.1.1 intelligibility ไว้ใน NFPA 72 ทดสอบใช้ได้ในเชิงพาณิชย์จะใช้เครื่องมือตรวจสอบ intelligibility4 3.4.1.2 สื่อสารด้วยเสียงมีผลบังคับใช้ภายในอาคารที่เกิดขึ้นโดยระบบออกแบบของลำโพงมาก มีความเข้มเสียงต่ำสุด4 3.4.2 ภาพอุปกรณ์เครือข่าย Strobes มีพื้นที่ทั้งหมดภายในการอาคารที่กำหนดถึง 1 ABAAG /1/ คนได้ยินพิการ Strobes มีที่ตำแหน่งเดียวกันในอาคารที่ต้องจะต้องเป็นอุปกรณ์แจ้งเตือนระบบเตือนไฟไหม้ รวม MNS/หิมะ ทองคำระบบอาจใช้แฟลช (ชัดเจน) หนึ่งหรือสอง strobes (ล้างไฟและแอมเบอร์สำหรับMNS) ตามแบบ AHJ4 3.4.2.1 ติดตั้งกองทัพเรือจะใช้แฟลชหนึ่งชัดเจน และยัง จะให้สัญญาณข้อความป้ายข้อความจะต้องผ่านประตูแต่ละ stairwell egress และผ่าน (หรือติดกับ)หมายถึงพบของ egress จากระดับการปล่อย ประตูทางออกภายนอกจากการห้องเดี่ยว (เช่น เครื่องกล หรือไฟฟ้าห้อง) ต้องมีเครื่องหมายข้อความ4 3.4.2.2 ติดตั้งกองทัพบกและกองทัพอากาศจะใช้แฟลชล้างไฟและตัวเหลืองแฟลชสำหรับ MNS ใช้ป้ายข้อความไม่ก็ได้ และที่ DODติดตั้ง ถ้าให้ ป้ายข้อความจะอยู่เหนือประตูสู่แต่ละ stairwell egressและสูง (หรือติดกับ) หมายถึงการพบของ egress จากระดับการปล่อยไม่มีประตูออกนอกจากห้องพักเดี่ยว (เช่น เครื่องกล หรือไฟฟ้าห้อง)ต้องมีเครื่องหมายข้อความ4 3.4.2.3 ติดตั้งนาวิกโยธินจะติดต่อ AHJ สำหรับคำแนะนำบน visualเครื่องแจ้งเตือนอินเตอร์เฟส 4 3.5 พื้นที่กว้าง MNS ถ้าตั้งให้บน MNSติดตั้ง DOD อาคารละ MNS สื่อสารกับตัวควบคุมกลางหน่วยของพื้นที่กว้าง MNS เพื่อแสดงข้อมูลสถานะ รับสั่ง เรียกใช้งานก่อนบันทึกข้อความ และข้อความเสียงสดมา ถ้าเป็นบริเวณไม่กว้าง MNSให้ในการติดตั้ง DOD อย่างน้อยที่สุด แต่ละอาคารจะ MNSสามารถรับสัญญาณเสียงเข้าระดับรายการ4 3.6 ตรรกะบล็อกไดอะแกรม ตัวเลข 4-1 และ 4-2 แสดงบล็อคทางตรรกะไดอะแกรมสำหรับโครงแบบที่ยอมรับได้ของแต่ละ MNS ใหม่ก่อสร้างหมายเหตุ: ไดอะแกรมเหล่านี้มีวัตถุประสงค์เพื่อแสดงเฉพาะความสัมพันธ์หน้าที่ของการส่วนประกอบที่สำคัญ พวกเขาไม่จำเป็นต้องเป็นสายไดอะแกรม จำเป็นมากไม่มีแสดงออกแบบคุณลักษณะสำหรับระบบการทำงาน เช่นสิ้นสุดของบรรทัด resistorsUFC 4-021-019 2551 เมษายนเปลี่ยนแปลง 1, 2553 มกราคม24รูป 4-1 อาคารแต่ละระบบแจ้งเตือนโดยรวม:ชุดระบบสัญญาณเตือนไฟไหม้และ MNS (กองทัพเรือ)แบตเตอรี่การสำรองข้อมูลรวมไฟปลุกควบคุมแผง&เขตปกครองตนเองควบคุมหน่วยลำโพงSTROBES (สีขาว/ใส)แสดง (ต้อง – กองทัพเรือ)ภายในคอนโซลการดำเนินงาน (S) (ถ้าใช้)ความนำต้องการตรวจสอบบริเวณกว้าง MNS(ถ้าอยู่)หมายเหตุรวมระบบ-สามารถใช้อย่าง น้อยหนึ่งเปลือกตามที่ปรากฏUFC 4-021-019 2551 เมษายนเปลี่ยนแปลง 1, 2553 มกราคม25รูปที่ 4-2 อาคารแต่ละระบบแจ้งเตือนโดยรวม:ชุดระบบสัญญาณเตือนไฟไหม้และ MNS (กองทัพบกและกองทัพอากาศ)แบตเตอรี่การสำรองข้อมูลรวมไฟปลุกควบคุมแผง&เขตปกครองตนเองควบคุมหน่วยความนำต้องการตรวจสอบภายในคอนโซลการดำเนินงานลำโพงSTROBES (สีเหลืองอำพัน)STROBES (สีขาว/ใส)แสดง (ถ้ามี)หมายเหตุรวมระบบ-สามารถใช้อย่าง น้อยหนึ่งเปลือกMNS พื้นที่กว้างเป็นที่อยู่(ถ้าอยู่)UFC 4-021-019 2551 เมษายนเปลี่ยนแปลง 1, 2553 มกราคม26ACU 4-4ตำแหน่งที่ตั้งของ 4-4.1 ACU จะสร้างระบบรวมกับหิมะทองคำ เหล่านี้แผงควบคุมอาจร่วมอยู่ในตู้เดียวกัน หรืออาจจะจริงแยกออก ถ้าอยู่ในตู้เดียวกัน ติดตั้งตู้ที่โดยปกติระบุคอมโพเนนต์ DOD AHJ สำหรับหิมะทองคำแบบสแตนด์อโลนคุณลักษณะการออกแบบ 4 4.2 ACU จะ:•สามารถทำงานได้อย่างอิสระตามบริเวณกว้าง MNS (ถ้าบริการในการติดตั้ง DOD)•มีระบบแสดงร่วมกับระบบเตือนภัยไฟไหม้ตามที่อธิบายไว้ในประชุม 864 มาตรฐาน UL และ NFPA 72 และข้อกำหนดเฉพาะนี้UFC การประเมินผลรายการจะดำเนินการ โดย UL โรงงานซึ่งกันและกันบริษัทวิจัย (FM), หรืออีกผลงานรู้จักการทดสอบห้องปฏิบัติการ (NRTL)N