In the investigated cases, the CCT is found to be underestimated
by the calculation method. For a real wind generator with
a high total inertia, it can be expected that the flux transient at
reclosing are of much more importance than the transients at
the moment the fault occurs, and that the calculated CCT will
be higher than what can be obtained from detailed investigations
[32]. To improve the accuracy of the calculation method
a possible future work could be to include the flux transients
at reclosing in a simplified way, by using a correction factor
accounting for the time needed to magnetize the machine as a
function of the system parameters.